NF2X Cable/NFA2X Bundle Conductor Cable Application
Self-supporting overhead cable bundle, applied for electric power distribution in low voltage metropolitan, suburban and rural networks, for public lighting and house connections. Laid on pillars, consoles and house fronts.NF2X Cable/NFA2X Bundle Conductor Cable Standard
HD 626 S1, VDE 0276-626Abbreviation
N - Standard Cable type
F - Facade Cable
A - Aluminium conductor
2X - XLPE insulation
+N - with 'Messenger' Core
Round stranded Conductor for all sizes connection derived from the distribution system.
Bundle Conductor Cable Construction
Conductor - NF2X: Stranded Copper Conductor - NFA2X: Stranded All Aluminium ConductorBundle Conductor Cable Insulation
Extruded of XLPE, capable for continuous operation at maximum cable's temperature
NF2X Cable PARAMETER
PHYSICAL PROPERTIES | ELECTRICAL PROPERTIES | |||||
Cable Size | Insulation Thickness | Approx.Twisted Diameter | Approx. Net.Weight | Max. Conductor Resistance at 20 ℃ | Current Carrying Capacity at 35℃ | Calculated Breaking Force |
mm2 | mm | mm | Kg/km | Ω/km | A | kg |
2x6rm | 1.2 | 13 | 147 | 3.08 | 54 | 394 |
2x10rm | 1.2 | 14 | 228 | 1.83 | 73 | 656 |
2x16rm | 1.2 | 16 | 350 | 1.15 | 97 | 1,051 |
4x6rm | 1.2 | 15.7 | 294 | 3.08 | 54 | 788 |
4x10rm | 1.2 | 170 | 455 | 1.83 | 73 | 1,312 |
4x16rm | 1.2 | 190 | 700 | 1.15 | 97 | 2,102 |
4x25rm | 1.4 | 240 | 1,072 | 0.727 | 133 | 3,284 |
NFA2X Cable PARAMETER
PHYSICAL PROPERTIES | ELECTRICAL PROPERTIES | |||||
Cable Size |
Insulation Thickness |
Approx. Twisted Diameter |
Approx. Net.Weight |
Max. Conductor Resistance at 20 ℃ |
Current Carrying Capacity at 35℃ |
Calculated Breaking Force |
mm2 | mm | mm | Kg/km | Ω/km | A | kg |
2x10rm | 1.2 | 14 | 94 | 3.08 | 54 | 322 |
2x16rm | 1.2 | 16 | 138 | 1.91 | 72 | 515 |
4x10rm | 1.2 | 17 | 187 | 3.08 | 54 | 644 |
4x16rm | 1.2 | 19 | 272 | 1.91 | 72 | 1030 |
4x25rm | 1.4 | 24 | 423 | 1.2 | 102 | 1610 |
4x35rm | 1.6 | 27 | 564 | 0.868 | 125 | 2250 |