YOUR CURRENT POSITION: Home > Product > Overhead Insulated Cable
ANSI/ICEA S-76-474 Overhead Service Drop Cable Aluminum Conductor

ANSI/ICEA S-76-474 Overhead Service Drop Cable Aluminum Conductor

IECA Standard Duplex/Triplex/Quadruplex Service Drop Cable

Overhead Service Drop Cable Application

This duplexed triplexed quadruplexed cable is suited for use as drop cable from a pole mounted transformer to the service entrance of a structure, or as secondary distribution between poles.  The cable should be limited to 600V phase to phase and not exceed 90˚C.
Triplex wire is commonly used for overhead, single phase service and contains three individual wires twisted around each other. The two insulated conductors are called the "hot" legs of the service while the bare (uninsulated) wire is the neutral wire of the service. As mentioned above, this triplexed cable is suited for use as drop cable from a pole mounted transformer to the service entrance of a structure, or as secondary distribution between poles.

Overhead Service Drop Cable Construction

Insulation made of cross-linked polyethylene, polyethylene, or compressed 1350-H19 conductor in concentrated strands.
Phase conductor:
Round, stranded, round conductor made of aluminum 1350
Phase Core Identification:
colour strip, rib or number
Neutral/Messenger conductor:
Bare AAC, ACSR, alloy 6201 AAAC
Insulation:
Black color polyethylene(PE) or cross-linked polyethylene(XLPE)

Overhead Service Drop Cable Standards

ASTM B-230:  Aluminum 1350-H19 wire for electrical purposes.
ASTM B-231:  Concentric lay stranded aluminum 1350 conductors.
ICEA S-76-474:  Neutral supported power cable assemblies with weather resistant extruded insulation rated at 600V.

ANSI/ICEA S-76-474 Standard Duplex Service Drop Wire Specification Physical and Electrical Performance Parameters

Bare AAC Neutral Messenger
Code Name Size Phase Conductor Strands Bare Neutral Messenger Strands Weight per 1000ft Ampacity
AAC Insul. Thick. Bare AAC Breaking Strength XLP Poly XLP Poly
No. Dia. No. Dia.
- AWG or kcmil - mm mm - mm Ib Ib Ib A A
Pekingese 1*6AWG+1*6AWG 1 4.11 1.14 7 1.56 563 63.5 61.7 85 70
Collie 1*6AWG+1*6AWG 7 1.56 1.14 7 1.56 563 66.8 63.1 85 70
Dachshund 1*4AWG+1*4AWG 1 5.19 1.14 7 1.96 881 95.5 93.4 115 90
Spaniel 1*4AWG+1*4AWG 7 1.96 1.14 7 1.96 881 100.5 95.4 115 90
Doberman 1*2AWG+1*2AWG 7 2.47 1.14 7 2.47 1350 152.7 145.7 150 120
Malemute 1*1/0AWG+1*1/0AWG 19 1.89 1.52 7 3.12 1990 242.6 234.2 205 160

 ANSI/ICEA S-76-474 Standard Triplex Service Drop Wire Size Physical and Electrical Performance Parameters

Bare AAC Neutral Messenger
Code Name Size Phase Conductor Strands Bare Neutral Messenger Strands Weight per 1000ft Service Drop Wire Ampacity
AAC Insul. Thick. Bare AAC Breaking Strength XLP Poly XLP Poly
No. Dia. No. Dia.
- AWG or kcmil - mm mm - mm Ib Ib Ib A A
Haiotis 2*6AWG+1*6AWG 1 4.11 1.14 7 4.11 563 102.5 98.8 85 70
Patella 2*6AWG+1*6AWG 7 1.56 1.14 7 1.56 563 109.1 101.6 85 70
Fusus 2*4AWG+1*4AWG 1 5.19 1.14 7 5.19 881 151.9 147.6 115 90
Oyster 2*4AWG+1*4AWG 7 1.96 1.14 7 1.96 881 161.8 151.7 115 90
Clam 2*2AWG+1*2AWG 7 2.47 1.14 7 2.47 1350 243.2 229.2 150 120
Murex 2*1/0AWG+1*1/0AWG 7 3.12 1.52 7 3.12 1990 395.1 369.4 205 160
Purpura 2*1/0AWG+1*1/0AWG 19 1.89 1.52 7 1.89 1990 386.1 369.4 205 160
Nassa 2*2/0AWG+1*2/0AWG 7 3.50 1.52 7 3.50 2510 485.8 455.3 235 185
Melita 2*3/0AWG+1*3/0AWG 19 2.39 1.52 19 2.39 3310 585.2 562.9 275 215
Portunus 2*4/0AWG+1*4/0AWG 19 3.25 1.52 19 3.25 4020 723.9 697.3 315 245
Nannynose 2*336.4kcmil+1*336.4kcmil 19 3.38 2.03 19 3.38 6146 1160.4 1118.0 420 325

ANSI/ICEA S-76-474 Standard Quadruplex Service Drop Cable Aluminum Conductor Physical and Electrical Performance Parameters

Bare AAC Neutral Messenger
Code Name Size Phase Conductor Strands Bare Neutral Messenger Strands Weight per 1000ft Service Drop Wire Ampacity
AAC Insul. Thick. Bare AAC Breaking Strength XLP Poly XLP Poly
No. Dia. No. Dia.
- AWG or kcmil - mm mm - mm Ib Ib Ib A A
Clydesdate 3*4AWG+1*4AWG 1 5.19 1.14 7 1.96 881 208.0 201.8 100 80
Pinto 3*4AWG+1*4AWG 7 1.96 1.14 7 1.96 881 223.0 207.9 100 80
Mustang 3*2AWG+1*2AWG 7 2.47 1.14 7 2.47 1350 333.0 312.6 135 105
Criollo 3*1/0AWG+1*1/0AWG 19 1.89 1.52 7 3.12 1990 529.0 504.5 180 140
Percheron 3*2/0AWG+1*2/0AWG 19 2.13 1.52 7 3.50 2510 649.0 620.5 205 160
Hanoverian 3*3/0AWG+1*3/0AWG 19 2.39 1.52 19 2.39 3310 799.0 765.6 235 185
Oldenburg 3*4/0AWG+1*4/0AWG 19 3.25 1.52 19 3.25 4020 986.0 946.7 275 210
Lippizaner 3*336.4kcmil+1*336.4kcmil 19 3.38 2.03 19 3.38 6146 1546.0 1519.2 370 280

Contact Us, Now.
24-hour service hotline
Contact online customer service
Add: Technology Building, Tongbai Road, Zhongyuan District, Zhengzhou, Henan, China.
Related products
ICEAS-61-402 Aluminum Covered Line Wire Weatherproof
ICEAS-61-402 Aluminum Covered Line Wire Weatherproof
ANSI/ICEA S-76-474 Overhead Service Drop Cable Aluminum Conductor
ANSI/ICEA S-76-474 Overhead Service Drop Cable Aluminum Conductor
POLY AL. POLY AAC POLY ACSR
POLY AL. POLY AAC POLY ACSR
IEC 60502-1 & TNB 0.6/1kV LV ABC Cable Aerial Bundle conductor
IEC 60502-1 & TNB 0.6/1kV LV ABC Cable Aerial Bundle conductor
Related cases
Single-Armored Plenum Tight Buffered Distribution Indoor/Outdoor Cable
Single-Armored Plenum Tight Buffered Distribution Indoor/Outdoor Cable
Single-Armored, Plenum, Tight Buffered Distribution Indoor/Outdoor CableTight buffered fibers are positioned in a flexible metal tube, which is filled with aram
AWAC Cable (AS/AC ) Wire for Africa
AWAC Cable (AS/AC ) Wire for Africa
AS/AC (AWAC) conductors are used as phase conductors to increase span length or clearances, neutral messengers for spacer cables, ground or shield wires, and as self-supporting cables.
Undersea-Submarine Fiber Optic Cable
Undersea/Submarine Fiber Optic Cable
The submarine cable is developed for deep-sea transoceanic systems. It is used to transmit optical signals and deliver electrical power to the wet plants. The f