YOUR CURRENT POSITION: Home > Product > Bare Conductor
AAAC Cables All Aluminum Alloy Conductor

AAAC Cables All Aluminum Alloy Conductor

kabel aaac; aaac factory
AAAC Conductor Application
AAAC is mainly used as bare overhead transmission cable and as primary and secondary distribution cable. It is also suitable for laying across basins, rivers and valleys where special geographical teatures exist. All aluminium alloy conductor(AAAC) is a special alloy with Magnesium and Silicium with an excellent conductivity value,specific mechanical resistance and high corrosion resistance.
AAAC Cable Standard
Basic design to BS 3242 / BS EN 50182 / IEC 61089 / ASTM B 399/B 399M / DIN 48201-6/AS 1531 standards
AAAC Wire Construction
AA-6101 aluminium alloy,Concentrically stranded
Max. Size 2500MCM, Max. str. No. 91Wires

All Aluminium Alloy Conductor Data Sheet

AAAC-IEC61089
Cross-section   Area Stranding   No. & Wire No.s Approx. Overall   Dia. Approx. Weight Rated strength Max. D.C.   resistance at 20℃
mm2 No.s mm mm Kg/km kN Ω/km
28.8 7 2.29 6.87 78.7 8.49 1.1453
46 7 2.89 8.67 125.9 13.58 0.7158
115 19 2.78 13.9 316.3 33.95 0.2877
460 37 3.98 27.86 1268.4 135.81 0.0721
1036 91 3.81 41.91 2861.1 305.58 0.0321
1439 91 4.49 49.39 3973.7 424.41 0.0231
AAAC-ASTM B399
Code Name Conductor   size Stranding   No. & Wire No.s Approx. Overall   Dia. Approx. Weight Rated strength Max. D.C.   resistance at 20℃
AWG (MCM) mm2 No.s mm mm Kg/km Kn Ω/km
Alton 48.69(4) 24.67 7 2.12 6.36 68 7.8 1.586
Azusa 123.3(1/0) 62.46 7 3.37 10.11 172 19.8 0.5365
Alliance 246.9   (4/0) 125.1 7 4.77 14.31 345 38.1 0.2678
Butte 312.8 158.5 19 3.26 16.3 437 48.8 0.2112
Canton 394.5 199 19 3.66 18.3 551 59 0.1676
  450 228 19 3.91 19.55 629 67.2 0.1468
AAAC-BS3242
Code Name Nominal   Cross-section Area Calculated   Cross-section Area Stranding   No. & Wire No.s Approx. Overall   Dia. Approx. Weight Rated Strength D.C. Resistance   at 20°C
mm2 mm2 No.s mm mm Kg/km Kn Ω/km
Hazel 50 59.87 7 3.3 9.9 165 16.8 0.5498
  70 84.05 7 3.91 11.73 232 23.5 0.3917
Ash 150 180.7 19 3.48 17.4 498 50.6 0.1831
Upas 300 362.1 37 3.53 24.71 998 101.4 0.09156
Walnut 350 421.8 37 3.81 26.67 1163 118.1 0.0786
Araucaria 700 821.1 61 4.14 37.26 2264 229.8 0.04047
AAAC-NFC34125
Code Cross-section   Area Stranding No Single wire dia. Approx. overall   dia. Approx. weight Rated tensile   strength 
mm2 No.s mm mm kg/km KN
55 54.6 7 3.15 9.45 149 17.75
153 152.8 19 3.2 16 417 49.66
323 312.6 37 3.28 22.96 853 101.6
475 475.4 61 3.15 28.35 1296 154.51
621 620.9 61 3.6 32.4 1693 201.79
926 926.3 91 3.6 32.4 2526 301.05

BS 3242

Code AL Nominal Area Cu Nominal Area Equivalent Total Area Stranding Overall Diameter Weight
  mm^2 mm^2 mm^2 No.×mm mm kg/km
- - 6.45 11.7 7/1.47 4.41 32.2
Box - 9.68 18.8 7/1.85 5.55 51.7
Acacia - 12.9 21.9 7/2.08 6.24 66.1
Almond 25 16.1 30.1 7/2.34 7.02 82.9
Ceda 30 19.4 35.5 7/2.54 7.62 97.8
- 40 22.6 42.2 7/2.77 8.31 116.4
Fir 50 25.8 47.8 7/2.95 8.85 131.8
Hazel 100 32.3 59.9 7/3.30 9.9 165
Pine - 38.7 71.7 7/3.61 10.83 197.7
- - 45.2 84.1 7/3.91 11.73 231.6
Willow 150 48.4 89.8 7/4.04 12.12 247.5
- 175 51.6 96.5 7/4.19 12.57 266.2
- 300 58.1 108.8 7/4.45 13.35 299.8
Oak - 64.5 118.9 7/4.65 13.95 327.8
- - 80.6 118.8 19/2.82 14.1 327.6
Mulberry - 96.8 151.1 19/3.18 15.9 416.7
Ash - 113 180.7 19/3.48 17.4 498.1
Elm - 129 211 19/3.76 18.8 582.1
Poplar - 145 239 37/2.87 20.09 658.8
- - 161 270.8 37/3.05 21.35 746.7
Sycamore - 194 303 37/3.23 22.61 834.9
Upas - 226 362.1 37/3.53 24.71 998.6
- - 258 421.8 37/3.81 26.47 1163
Yew - - 479.9 37/4.06 28.42 1323

(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.

BS EN 50182

Code Stranding Nominal Area Overall Diameter Weight Rated Strength Electrical Resistance Current Rating*
  No.×mm mm^2 mm kg/km KN Ω/Km A
Box 7/1.85 18.8 5.55 51.4 5.55 1.748 87
Acacia 7/2.08 23.8 6.24 64.9 7.02 1.3828 101
Almond 7/2.34 30.1 7.02 82.2 8.88 1.0926 116
Cedar 7/2.54 35.5 7.62 96.8 10.46 0.9273 129
Deodar 7/2.77 42.2 8.31 115.2 12.44 0.7797 143
Fir 7/2.95 47.8 8.85 130.6 14.11 0.6875 155
Hazel 7/3.30 59.9 9.9 163.4 17.66 0.5494 178
Pine 7/3.61 71.6 10.83 195.6 21.14 0.4591 199
Holly 7/3.91 84.1 11.73 229.5 24.79 0.3913 219
Willow 7/4.04 89.7 12.12 245 26.47 0.3665 228
Oak 7/4.65 118.9 13.95 324.5 35.07 0.2767 272
Mulberry 19/3.18 150.9 15.9 414.3 44.52 0.2192 314
Ash 19/3.48 180.7 17.4 496.1 53.31 0.183 351
Elm 19/3.76 211 18.8 579.2 62.24 0.1568 386
Poplar 37/2.87 239.4 20.09 659.4 70.61 0.1387 416
Sycamore 37/3.23 303.2 22.61 835.2 89.4 0.1095 480
Upas 37/3.53 362.1 24.71 997.5 106.82 0.0917 535
Yew 37/4.06 479 28.42 1319.6 141.31 0.0693 633
Totara 37/4.14 498.1 28.98 1372.1 146.93 0.0666 648
Rubus 61/3.50 586.9 31.5 1622 173.13 0.0567 714
Sorbus 61/3.71 659.4 33.39 1822.5 194.53 0.0505 764
Araucaria 61/4.14 821.1 37.26 2269.4 242.24 0.0406 868
Redwood 61/4.56 996.2 41.04 2753.2 293.88 0.0334 970

Note: *The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.

IEC 61089

Code Nominal Area Stranding Overall Diameter Weight Rated Strength Electrical Resistance Current Rating*
  mm^2 No.×mm mm kg/km KN Ω/Km A
16 18.4 18.4 5.49 50.4 5.43 1.7896 86
25 28.8 28.8 6.87 78.7 8.49 1.1453 113
40 46 46 8.67 125.9 13.58 0.7158 151
63 72.5 72.5 10.89 198.3 21.39 0.4545 200
100 115 115 13.9 316.3 33.95 0.2877 266
125 144 144 15.5 395.4 42.44 0.2302 305
160 184 184 17.55 506.1 54.32 0.1798 355
200 230 230 19.65 632.7 67.91 0.1439 407
250 288 288 21.95 790.8 84.88 0.1151 466
315 363 363 24.71 998.9 106.95 0.0916 535
400 460 460 27.86 1268.4 135.81 0.0721 618
450 518 518 29.54 1426.9 152.79 0.0641 663
500 575 575 31.15 1585.5 169.76 0.0577 706
560 645 645 33.03 1778.4 190.14 0.0516 755
630 725 725 35.01 2000.7 213.9 0.0458 809
710 817 817 37.17 2254.8 241.07 0.0407 866
800 921 921 39.42 2540.6 271.62 0.0361 928
900* 1036 1036 41.91 2861.1 305.58 0.0321 992
1000* 1151 1151 44.11 3179 339.53 0.0289 1051
1120* 1289 1289 46.75 3560.5 380.27 0.0258 1118
1250* 1439 1439 49.39 3973.7 424.41 0.0231 1185

(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.

ASTM B 399/B 399M

Nominal Area Stranding Overall Diameter Weight Rated Strength Electrical Resistance Current Rating*
AWG&MCM mm^2 No.×mm mm kg/km KN Ω/Km A
6 13.2 7/1.55 4.65 36.2 4.18 2.5361 69
4 21.1 7/1.96 5.88 57.9 6.69 1.586 93
2 33.5 7/2.47 7.41 92 10.6 0.9987 123
0 53.5 7/3.12 9.36 146.8 17 0.62592 165
2/0 67.3 7/3.50 10.5 184.8 20.4 0.49738 190
3/0 84.9 7/3.93 11.79 233 25.7 0.3945 219
4/0 107 7/4.42 13.26 294.7 32.5 0.31188 253
250 126 19/2.91 14.55 346.7 38.8 0.26509 280
300 152 19/3.19 15.95 416.7 46.6 0.22059 313
350 178 19/3.45 17.25 487.3 52 0.1886 345
400 203 19/3.69 18.45 557.5 59.5 0.16486 375
450 228 19/3.91 19.55 626 66.8 0.14683 402
500 253 19/4.12 20.6 695 74.2 0.13224 429
550 279 37/3.10 21.7 766.2 83.9 0.11995 455
600 303 37/3.23 22.61 831.9 91 0.11049 478
650 330 37/3.37 23.59 905.5 94.9 0.1015 504
700 354 37/3.49 24.43 971.2 101 0.09464 525
750 381 37/3.62 25.34 1045 109 0.08796 549
800 404 37/3.73 26.11 1109 116 0.08285 569
900 456 37/3.96 27.72 1250 131 0.07351 612
1000 508 37/4.18 29.26 1393 146 0.06597 653
1250 631 61/3.63 32.67 1732 179 0.05306 743
1500 759 61/3.98 35.82 2082 215 0.04414 827
1750 886 61/4.30 38.7 2431 251 0.03781 904

(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.

DIN 48201 Part 6

Nominal Area Stranding Overall Diameter Weight Rated Strength Electrical Resistance Current Rating*
Nominal Teorical
mm^2 mm^2 No.×mm mm kg/km KN Ω/Km A
16 15.89 7/1.70 5.1 43 4.44 2.0742 78
25 24.25 7/2.10 6.3 66 6.77 1.3593 102
35 34.36 7/2.50 7.5 94 9.6 0.9591 126
50 49.48 7/3.00 9 135 13.82 0.666 158
50 48.35 19/1.80 9 133 13.5 0.6849 156
70 65.81 19/2.10 10.5 181 18.38 0.5032 189
95 93.27 19/2.50 12.5 256 26.05 0.3551 234
120 116.99 19/2.80 14 322 32.68 0.2831 269
150 147.11 37/2.25 15.8 406 41.09 0.2256 309
185 181.62 37/2.50 17.5 500 50.73 0.1828 352
240 242.54 61/2.25 20.3 670 67.74 0.1371 420
300 299.43 61/2.50 22.5 827 83.63 0.111 477
400 400.14 61/2.89 26 1104 111.76 0.0831 568
500 499.83 61/3.23 29.1 1379 139.6 0.0665 649
625* 626.2 91/2.96 32.6 1732 174.9 0.0531 742
800* 802.09 91/3.35 36.9 2218 224.02 0.0415 857
1000* 999.71 91/3.74 41.1 2767 279.22 0.0333 971

* The items marked with “*” are not in our current product range and the details are for information only.

(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.

All Aluminum Alloy 1120 AAAC/1120 [AS 1531 - Standard]

CODENAME

AAAC1120

Construction

Calculation cross-section

Approx.Over all diameter

Approx.Over all weight

Maximum DC resistance at 20oC

Calculated breaking load

Equivalent Aluminum area

 

No. x mm

mm2

mm

kg/km

Ω/km

kN

mm2

Chlorine

7 x 2.50

34.36

7.50

94.3

0.864

8.18

32.8

Chromium

7 x 2.75

41.58

8.25

113

0.713

9.91

39.7

Fluorine

7 x 3.00

49.48

9.00

135

0.599

11.8

47.2

Helium

7 x 3.75

77.28

11.3

211

0.383

17.6

73.7

Hydrogen

7 x 4.50

111.3

13.5

304

0. 266

24.3

106

Iodine

7 x 4.75

124.0

14.3

339

0.239

27.1

118

Krypton

19 x 3.25

157.6

16.3

433

0.189

37.4

150

Lutetium

19 x 3.50

182.8

17.5

503

0.163

41.7

173

Neon

19 x 3.75

209.8

18.8

576

0.142

47.8

199

Nitrogen

37 x 3.00

261.6

21.0

721

0.114

62.2

248

Nobelium

37 x 3.25

307.0

22.8

845

0.097 3

72.8

291

Oxygen

19 x 4.75

336.7

23.8

924

0.088 4

73.6

320

Phosphorus

37 x 3.75

408.5

26.3

1,120

0.073 1

93.1

387

Selenium

61 x 3.25

506.1

29.3

1,400

0.059 2

114

478

Silicon

61 x 3.50

586.9

31.5

1,620

0.051 1

127

555

Sulfur

61 x 3.75

673.7

33.8

1,860

0.044 4

145

636

All Aluminum Alloy 6201 AAAC/6201 [AS 1531 - Standard]

CODENAME

AAAC6201

Construction

Calculation cross-section

Approx.Over all diameter

Approx.Over all weight

Maximum DC resistance at 20oC

Calculated breaking load

Equivalent Aluminum area

 

No. x mm

mm2

mm

kg/km

Ω/km

kN

mm2

Diamond

7 x 2.50

34.36

7.50

94.3

0.967

9.64

29.3

Dolomite

7 x 2.75

41.58

8.25

113

0.799

11.6

35.4

Emerald

7 x 3.00

49.48

9.00

135

0.671

13.9

42.2

Garnet

7 x 3.75

77.28

11.3

211

0.430

21.7

65.8

Jade

7 x 4.50

111.3

13.5

304

0.298

31.2

94.8

Jasper

7 x 4.75

124.0

14.3

339

0.268

34.8

106

Opal

19 x 3.25

157.6

16.3

433

0.212

44.2

134

Patronite

19 x 3.50

182.8

17.5

503

0.183

51.3

155

Pearl

19 x 3.75

209.8

18.8

576

0.159

58.8

178

Ruby

37 x 3.00

261.6

21.0

721

0.128

73.5

221

Ruthenium

37 x 3.25

307.0

22.8

845

0.109

86.1

260

Rutile

19 x 4.75

336.7

23.8

924

0.099 1

94.4

285

Sapphire

37 x 3.75

408.5

26.3

1,120

0.081 9

115

345

Spinel

61 x 3.25

506.1

29.3

1,400

0.066 2

135

427

Tantalum

61 x 3.50

586.9

31.5

1,620

0.057 2

156

495

Topaz

61 x 3.75

673.7

33.8

1,860

0.049 8

179

568


Contact Us, Now.
24-hour service hotline
Contact online customer service
Add: Technology Building, Tongbai Road, Zhongyuan District, Zhengzhou, Henan, China.
Related products
Cable Almelec AAAC - All Aluminium Alloy Aster Conductor NFC
Cable Almelec AAAC - All Aluminium Alloy Aster Conductor NFC
AAC All Aluminum Conductors
AAC All Aluminum Conductors Bare Aerial Conductors
ACSR-Aluminum Conductor Steel Reinforced
ACSR-Aluminum Conductor Steel Reinforced
GSW Cable/Guy Wire/Stay Wire/ Earth Wire
GSW Cable/Guy Wire/Stay Wire/ Earth Wire
Related cases
Undersea-Submarine Fiber Optic Cable
Undersea/Submarine Fiber Optic Cable
The submarine cable is developed for deep-sea transoceanic systems. It is used to transmit optical signals and deliver electrical power to the wet plants. The f
 OPGW-48B4-226 [93.8;496.1] Price for Kenya
OPGW-48B4-226 [93.8;496.1] Price for Kenya
OPGW-48B4-226 [93.8;496.1] Price for Kenya OPGW Cable SpecificationsCable Type: OPGW-48B4-226 [93.8;496.1] OPGW-48B4-226 Structure Structure Materi
Indoor Cable Riser or Plenum Rated
Indoor Cable Riser or Plenum Rated
Indoor Cable Riser or Plenum RatedIndoor tight buffered cables assure reliable broadband performance, meet flame retardant safety codes, and support easy field