PVC Insulated Power Cable
This product is used for power transmission and distribution lines with AC rated voltage of 1.8/3V and below.Its mechanical and physical properties and electrical performance meet the requirements of national standard GB/T12706- 2008 and international standard IEC60502-2004 “Extruded Insulated Power Cable with Rate Voltage of 1-30KV and Accessories”.
PVC Insulated Power Cable Operating characteristics and electrical performance
1. Cable laying temperature: ≥0°C2. Long-term allowable operating temperature of cable conductor: ≤70°C
3. Higest working temperature of cable in case of short circuit (the longest lasting time is not over 5s): 160°C
4. Minimum permissible bending radius: Single core cable: 20D; multi-core cable: 15D (Note: D is actual outer diameter of cable).
5. AC withstand voltage test of finished cable product.
Rated voltage (KV) | 0.6/1 | 1.8/3 |
Rated voltage (KV) | 3.5 | 6.5 |
Duration (min) | 5 | 5 |
Occasions of PVC Insulated Power Cable
Model | Name |
Laying Occasion |
|
Copper core | Aluminum core | ||
VV | VLV | PVC insulated and sheathed power cable | Laid indoors, and in tunnels, pipelines, cable trenches, and flammable and severe corrosion places, and can not bear external mechanical forces. |
VY | VLY | PVC insulated PE sheathed power cable | Laid indoors, and in pipelines, cable trenches and severe corrosion places, and cannot bear external mechanical forces |
VV22 | VLV22 | PVC insulated steel tape armored PVC sheathed power cable | Laid indoors, and in cable trenches, underground severe corrosion places, and cannot bear tension. |
VV23 | VLV23 | PVC insulated steel tape armored PE | Laid indoors, and in cable trenches and underground severe corrosion place, and cannot bear tension. |
VV32 | VLV32 | PVC insulated thin steel wire armored PVC sheathed power cable | Laid under ground and in shafts, water and severe corrosion places, and cannot bear high tension. |
VV33 | VLV33 | PVC insulated thin steel wire armored PVC sheathed power cable | Laid under ground and in shafts, water and severe corrosion places, and can bear high tension. |
VV42 | VLV42 | PVC insulated thick steel wire armored PVC sheathed power cable | Laid under ground and in shafts and severe corrosion places, and can bear high tension. |
VV43 | VLV43 | PVC insulated thick steel wire armored PE sheathed power cable | Laid under ground and in shafts and severe corrosion places, and can bear high tension. |
PVC Insulated Power Cable Range of production
Number of cores Cross sectional Voltage level area (mm2) |
0.6/1 |
1.8/3 |
Single core 1 | 1.5-100 | 10-1000 |
Twin core 2 | 1.5-240 | 10-240 |
Triple core 3 | 1.5-300 | 10-300 |
Three big cores and one small core 3+1 | 2.5-300 | 10-300 |
Fourth core 4 | 2.5-300 | 10-300 |
Fifth core 5 | 2.5-300 | 10-300 |
Three big cores and two small cores 3+2 | 2.5-300 | 10-300 |
Four big cores and one small core 4+1 | 2.5-300 | 10-300 |
XLPE insulated power cable for 1.8/3KV and below
The product is applicable for AC 50Hz transmission and distribution lines with rated voltage of 1.8/3KV or below.The mechanical properties and electrical performance of cables meet the requirements of national standard GB/T12706- 2008 and international standards IEC60502-2005.
XLPE insulated power cable Operating characteristics
1. Cable laying temperature: ≥0°C2. Cable conductor long-term allowable working temperature:≤90°C
3. Higest working temperature of cable in case of short circuit (the longest lasting time is not over 5s): 250°C
4. Minimum allowable bending radius: Single core cable: 20D mm; multi-core cable: 15D mm Note: D is actual outer diameter of the cable
XLPE insulated power Cable models, names, and laying occasions
Model | Name |
Laying Occasion |
|
Copper core | Aluminum core | ||
YJV | YJLV | XLPE insulated PVC sheathed power cable | Laid indoors, and in tunnels and pipelines |
YJY | YJLY | XLPE insulated PE sheathed power cable | |
YJV22 | YJLV22 | XLPE insulated steel tape armored PVC sheathed power cable | Adapt for buried laying, not suitable for in-pipe laying |
YJV23 | YJLV23 | XLPE insulated steel tape armored PE sheathed power cable | |
YJV32 | YJLV32 | XLPE insulated thin steel wire armored PVC sheathed power cable | Laid on riverbeds of rivers or shallow water as connecting lines across rivers or petroleum/natural gas platforms, also used in land high drop areas. |
YJV33 | YJLV33 | XLPE insulated thin steel wire armored PVC sheathed power cable | |
YJV42 | YJLV42 | XLPE insulated thick steel wire armored PVC sheathed power cable | |
YJV43 | YJLV43 | XLPE insulated thick steel wire armored PE sheathed power cable |
XLPE insulated power cable Range of production
Number of cores Cross sectional area (mm2) |
0.6/1 |
1.8/3 |
Single core 1 | 1.5-1000 | 10-1000 |
Twin core 2 | 1.5-240 | 10-240 |
Triple core 3 | 1.5-300 | 10-300 |
Three big cores and two small cores 3+2 | 2.5-300 | 10-300 |
PVC insulated cables with rated voltage of 450/750V and below
This product is suitable for power, household appliances, instruments, small power tools, dynamic lighting and other applications with AC rated voltage (Uo/U) of 450/750V and below.PVC insulated cables with rated voltage of 450/750V and below Operating characteristics
1. Laying temperature: ≥0°C2. Cable operating temperature: except 60227IEC07 (BV-90) and 60227IEC08 (RV-90), the maximum operating temperature is 90°C [the rest are 70°C].
3. Allowable bending radius: for cables with outer diameter (D) less than 25mm, should be not less than 4D; for cables with outer diameter (D) 25mm and above, should not be less than 6D.
Table of models, names and specifications of PVC insulated cables with rated voltage of 450/750V and below.
Model | Original mode | Product name | Specificaiton (mm2) |
60227IEC01 | BV | Single core hard conductor non-sheathed cable for general pupose | 1 core 1.5-400 |
60227IEC02 | RV | Single core soft conductor non-sheathed cable for general pupose | 1 core 1.5-240 |
60227IEC05 |
BV |
Single core solid conductor non-sheathed cable (conductor temperature of 70°C) for internal wiring | 1 core 0.5-1.0 |
60227IEC06 |
RV |
Single core solid conductor non-sheathed cable (conductor temperature of 70°C) for internal wiring | 1 core 0.5-1.0 |
60227IEC07 |
BV-90 |
Single core solid conductor non-sheathed cable (conductor temperature of 90°C) for internal wiring | 1 core 0.5-2.5 |
60227IEC08 |
RV-90 |
Single core solid conductor non-sheathed cable (conductor temperature of 90°C) for internal wiring | 1 core 0.5-2.5 |
60227IEC10 | BVV | Light PVC sheathed cable | 2-5 cores 1.5-35 |
60227IEC43 | SVR | Fleixible wire for indoor decorative lighting circuit | 1 core 0.5-0.75 |
60227IEC52 | RVV | Light PVC sheathed cable | 2-3 cores 0.5-0.75 |
60227IEC53 | RVV | Ordinary PVC sheathed flexible wire | 2-5 cores 0.75-2.5 |
60227IEC74 | RVVYP | Oil resistant PVC sheathed screened flexible cable | 2-60 cores 0.5-2.5 |
60227IEC75 | RVVY | Oil resistant PVC sheathed screened flexible cable | 2-60 cores 0.5-2.5 |
BLV | Aluminum core PVC insulated cable | 1 core 2.5-400 | |
BVV | Aluminum core PVC insulated PVC sheathed round cable | 1 core 0.75-10 | |
BLVV | Aluminum core PVC insulated PVC sheathed round cable | 1 core 2.5-10 | |
BLVVB | Aluminum core PVC insulated and sheathed parallel cable | 2-3 cores 2.5-10 | |
BVVB | Steel core PVC insulated and sheathed round cable | 2-3 cores 0.75-10 | |
BVR | Copper core PVC insulated flexible cable | 1 core 2.5-10 | |
BVVR | Copper core PVC shielded PVC sheathed flexible cable | 1-3c ores 0.5-2.5 |
PVC insulated control cable
This product is used for electrical appliance and instrument connecting cables in power distribution equipment with AC rated voltage of 450/750V and below.Its mechanical and physical properties and electrical performance meet the requirements of GB/T9330-2008 "Plastic Insulated Control Cable.
PVC Insulated Control Cable Operating characteristics
1. Cable laying temperature: ≥0°C2. Long-term allowable operating temperature of cable conductor: 70°C
3. Minimum permissible bending radius:
a. For unarmored cables, should be no less than six times of cable outer diameter;
b. For armored or copper belt shield structure cables, should be not less than 12 times of cable outer diameter;
c. For flexible cable with shield structure, shoud be less than six times of cable outer diameter.
4. Finished cable can bear AC 5HZ, 3KV, 5min withstand test without breakdown.
5. Conductor DC resistance meets the requirements of national standard GB/T3956-2008 “Cable Conductor” and international standard IEC60228.
PVC Insulated Control Cable Models, Names and Laying Occasions
Model | Name | Laying Occasion |
KVV | Copper core PVC insulated PVC sheathed control cable | Laid indoors, and in cable trenches, pipelines and other fixed occasions. |
KVVP | Copper core PVC insulated PVC sheathed braid shield control cable | Laid indoors, and in cable trenches, pipelines and other fixed occasions requiring shielding. |
KVVP2 | Copper core PVC insulated PVC sheathed braid shield control cable | Laid indoors, and in cable trenches, pipelines and other fixed occasions requiring shielding. |
KVV22 | Copper core PVC insulated PVC sheathed copper belt shield control cable | Laid indoors, and in cable trenches, pipelines, direct-buring and other fixed places capable of bearing large mechanical force. |
KVV32 | Copper core PVC insulated PVC sheathed steel tape armored control cable | Laid indoors, and in cable trenches, pipelines, vertical shafts and other fixed places capable of bearing large mechanical force. |
KVVR | Copper core PVC insulated PVC sheathed, fine steel wire armored control cable | Laid indoors in occasions requiring movement and flexibility. |
KVVRP | Copper core PVC insulated PVC sheathed flexible control cable | Laid indoors in occasions requiring movement, flexibility and shielding. |
KVVP2-22 | Copper core PVC insulated PVC sheathed copper belt shield steel tape armored control cable | Laid indoors, and in cable trenches, pipelines and other fixed occasions capable of bearing large mechanical force and requiring shielding. |
PVC Insulated Control Cable Range of production
Model |
Rated voltage (V) | Conductor nominal cross sectional area (mm2) | |||||||
0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 | |||
KV | 450/750 |
- | 2-61 | 2-14 | 2-10 | ||||
KVVP | |||||||||
KVVP2 | 4-61 | 4-14 | 4-10 | ||||||
KVV22 | - | 7-61 | 4-61 | 4-14 | 4-10 | ||||
KVVP2-22 | |||||||||
KVV32 | - | 19-61 | 7-61 | 4-14 | 4-10 | ||||
KVVR | 4-61 | - | - | ||||||
KVVRP | 4-61 | 4-48 | - | - |
XLPE Insulated Control Cable
This product is used for electrical appliance and instrument connecting cables in power distribution equipment with AC rated voltage of 450/750 V and below.Its mechanical and physical properties and electrical performance meet the requirements in GB/T9330-2008 "XLPE Insulated Control Cable”.
Operating characteristics and electrical performance
1. Cable laying temperature: ≥0°C2. Long-term allowable operating temperature of cable conductor: 90°C
3. Minimum permissible bending radius:
a. For unarmored cables, should be no less than 6 times of cable outer diameter;
b. For armored or copper belt shield structure cables, should be not less than 12 times of cable outer diameter;
c. For flexible cable with shield structure, shoud be less than six times of cable outer diameter.
4. Finished cable can bear AC 50HZ, 3 KV, 5min withstand test without breakdown.
5. Conductor DC resistance meets the requirements of national standard GB/T3956-2008 “Cable Conductor” and international standard IEC60228.
Models, Names and Laying Occasions of XLPE Insulated Control Cable
Model | Name | Laying Occasion |
KYJV | Copper core XLPE insulated PVC sheathed control cable | Laid indoors, and in cable trenches, pipelines and other fixed occasions. |
KYJVP | Copper core XLPE insulated PVC sheathed braid shield control cable | Laid indoors, and in cable trenches, pipelines and other fixed occasions requiring shielding. |
KYJVP2 | Copper core XLPE insulated PVC sheathed copper belt shield control cable | Laid indoors, and in cable trenches, pipelines and other fixed occasions requiring shielding. |
KYJV22 | Copper core XLPE insulated PVC sheathed steel tape armored control cable | Laid indoors, and in cable trenches, pipelines, direct-buring and other fixed places capable of bearing large mechanical force. |
KYJV32 | KYJV32 Copper core XLPE insulated PVC sheathed fine steel wire armored control cable | Laid indoors, and in cable trenches, pipelines, vertical shafts and other fixed places capable of bearing large mechanical force. |
KYJVR | Copper core XLPE insulated PVC sheathed flexible control cable | Laid indoors in occasions requiring movement and flexibility. |
KYJVRP | Copper core XLPE insulated PVC sheathed braid shielding control cable | Laid indoors in occasions requiring movement, flexibility and shielding. |
KYJVP2-22 | Copper core XLPE insulated PVC sheathed steel tape shielded steel plate armored control cable | Laid indoors, and in cable trenches, pipelines and other fixed occasions capable of bearing large mechanical force and requiring shielding. |
XLPE Insulated Control Cable Range of production
Model |
Rated voltage (V) | Conductor nominal cross sectional area (mm2) | |||||||
0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 | |||
KYJV | 45O/750 |
- | 2-61 | 2-14 | 2-10 | ||||
KYJVP | |||||||||
KYJP2 | 4-61 | 4-14 | 4-10 | ||||||
KYJV22 | - | 7-61 | 4-61 | 4-14 | 4-10 | ||||
KYJVP2-22 | |||||||||
KYJV32 | - | 19-61 | 7-61 | 4-14 | 4-10 | ||||
KYJVR | 4-61 | - | - | ||||||
KYJVRP | 4-61 | 4-48 | - | - |
0.6/1KV PVC/PVC Power cable (non-armored) VV, VLV
Conductor dimensions (mm2) |
Insulation thickness (mm) |
Nonmetallic sheath, unarmored cable | |||||||||||||||||||
Sheath thickness | Outer diameter (approximate) | Cable weight (Kg/km) | |||||||||||||||||||
mm | mm | Copper core | Aluminum core | ||||||||||||||||||
1C | 2C | 3C | 4C | 5C | 1C | 2C | 3C | 4C | 5C | 1C | 2C | 3C | 4C | 5C | 1C | 2C | 3C | 4C | 5C | ||
1.5 | 0.8 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 5.8 | 10.4 | 10.8 | 11.6 | 12.4 | 49 | 131 | 152 | 184 | 215 | 40 | 113 | 124 | 147 | 168 |
2.5 | 0.8 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 6.2 | 11.2 | 11.7 | 12.6 | 13.5 | 62 | 159 | 191 | 234 | 277 | 47 | 128 | 144 | 172 | 199 |
4 | 1.0 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 7.1 | 12.9 | 13.6 | 14.7 | 15.9 | 86 | 211 | 264 | 330 | 391 | 62 | 161 | 189 | 231 | 266 |
6 | 1.0 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 7.6 | 13.9 | 14.7 | 15.9 | 17.3 | 110 | 268 | 334 | 423 | 505 | 73 | 193 | 221 | 273 | 318 |
10 | 1.0 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 8.7 | 16.2 | 17.1 | 18.6 | 20.3 | 158 | 380 | 492 | 627 | 754 | 96 | 254 | 303 | 375 | 439 |
16 | 1.0 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 9.8 | 18.4 | 19.5 | 21.3 | 23.3 | 224 | 533 | 714 | 905 | 1094 | 124 | 331 | 412 | 502 | 590 |
25 | 1.2 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 11.2 | 21.2 | 22.5 | 24.7 | 27.1 | 325 | 759 | 1019 | 1307 | 1592 | 169 | 445 | 547 | 678 | 806 |
35 | 1.2 | 1.4 | 1.8 | 1.8 | 1.8 | 1.9 | 12.4 | 23.6 | 21.4 | 27.6 | 30.5 | 429 | 974 | 1313 | 1699 | 2098 | 211 | 533 | 652 | 818 | 997 |
50 | 1.4 | 1.4 | 1.8 | 1.8 | 1.9 | 2.1 | 14.0 | 26.8 | 28.0 | 31.6 | 35.2 | 590 | 1265 | 1781 | 2354 | 2929 | 278 | 636 | 837 | 1096 | 1355 |
70 | 1.4 | 1.4 | 1.9 | 2.0 | 2.1 | 2.2 | 15.6 | 23.4 | 27.2 | 31.5 | 37.9 | 791 | 1650 | 2393 | 3155 | 3942 | 353 | 770 | 1071 | 1394 | 1740 |
95 | 1.6 | 1.5 | 2.0 | 2.1 | 2.2 | 2.4 | 17.9 | 27.2 | 31.4 | 36.6 | 43.0 | 1062 | 2206 | 3205 | 4239 | 5295 | 467 | 1011 | 1412 | 1849 | 2307 |
120 | 1.6 | 1.5 | 2.1 | 2.2 | 2.4 | 2.5 | 19.3 | 29.8 | 34.3 | 39.2 | 46.9 | 1306 | 2727 | 3966 | 5244 | 6549 | 555 | 1217 | 1701 | 2224 | 2774 |
150 | 1.8 | 1.6 | 2.2 | 2.3 | 2.5 | 2.7 | 21.4 | 32.6 | 37.9 | 43.1 | 52.4 | 1625 | 3374 | 4924 | 6508 | 8155 | 686 | 1486 | 2093 | 2733 | 3437 |
185 | 2.0 | 1.7 | 2.4 | 2.5 | 2.7 | 2.9 | 23.7 | 38.6 | 42.3 | 48.2 | 60.7 | 1998 | 4185 | 6062 | 8022 | 10074 | 840 | 1857 | 2571 | 3366 | 4254 |
240 | 2.2 | 1.8 | 2.6 | 2.7 | 2.9 | 3.1 | 26.5 | 43.8 | 49.7 | 55.7 | 65.8 | 2565 | 5371 | 7825 | 10335 | 12911 | 1062 | 2351 | 3296 | 4295 | 5361 |
300 | 2.4 | 1.9 | 2.7 | 2.9 | 3.1 | 3.3 | 29.3 | 48.8 | 52.8 | 62.3 | 71.4 | 3186 | 6641 | 9696 | 12859 | 16023 | 1306 | 2854 | 4016 | 5285 | 6557 |
400 | 2.6 | 2.0 | 3.1 | 3.4 | 3.7 | 33.0 | 59.8 | 71.2 | 83.1 | 4191 | 12739 | 16940 | 21124 | 1684 | 5165 | 6842 | 8501 | ||||
500 | 2.8 | 2.1 | 3.4 | 3.4 | 36.4 | 74.2 | 82.2 | 86.5 | 5198 | 15898 | 20937 | 2064 | 6431 | 8314 | |||||||
630 | 2.8 | 2.2 | 40.1 | 77.0 | 85.3 | 6464 | 2515 | ||||||||||||||
800 | 2.8 | 2.3 | 45.2 | 8126 | 3112 | ||||||||||||||||
1000 | 3.0 | 2.5 | 50.5 | 10120 | 3853 |