U-1000 R2V & RVFV Cables for Algeria
U-1000 R2V & RVFV Cables
Industry: Building & Construction, Transmission, Distribution & Power Networks
Standard: NF C32-322
Type: Armoured Cable – SWA & AWA, Industrial Cable, Power Network & Local Distribution Cable
Our U-1000 cables are manufactured in accordance with French Norms (U-1000 R2V: NF C 32-322 / U-1000 RVFV: NF C 32-321). They are low voltage fixed wiring in armoured and unarmoured variants.
R2V and RVFV Cable Specification
R2V cable (also known as XV or RV cable) are rigid unarmoured power and control cables, whilst U-1000 RVFV cable (also known as XAV cable) are the armoured equivalent. They are used for the supply of electricity in a wide range of semi-industrial and industrial applications with a voltage rating of 600/1000V. This including lighting remote control and telecontrol installation systems, and other electrical devices.
The U-1000 R2V cable can be fixed on cable trays, within conduits or to walls. The U-1000 RVFV is constructed with additional two layers of steel tape armouring and so can also be used outdoors and in direct burial installations or where additional protection against mechanical stresses is required. The U-1000 RVFV is not recommended for burial in areas that are flooded for more than two months per year or in trenches used as drains.
R2V & RVFV Cables Construction Table
|
U-1000 R2V/ XV/ RV CABLE |
U-1000 RVFV / XAV XLPE PVC 0.6/1KV CABLE |
VOLTAGE |
0.6/1kV |
CONDUCTOR |
Class 1 Solid or Class 2 Stranded Copper |
INSULATION |
XLPE (Cross-Linked Polyethylene) |
INNER SHEATH |
PVC (Polyvinyl Chloride) |
ARMOUR |
- |
Two Steel Tapes |
OUTER SHEATH |
PVC-FR (Polyvinyl Chloride Flame Retardant) |
PVC (Polyvinyl Chloride) |
0.6 / 1 kV U-1000 RVFV Cable Parameter
NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA |
NOMINAL OVERALL DIAMETER |
NOMINAL WEIGHT |
mm2 |
mm |
kg/km |
2 |
1.5 |
13 |
215 |
2 |
2.5 |
14 |
249 |
2 |
4 |
15.5 |
309 |
2 |
6 |
16.5 |
386 |
2 |
10 |
18.5 |
515 |
2 |
16 |
20.5 |
709 |
2 |
25 |
23.5 |
1063 |
3 |
2.5 |
14.5 |
274 |
3 |
4 |
16 |
352 |
3 |
6 |
17.5 |
447 |
3 |
10 |
19 |
624 |
3 |
16 |
22 |
849 |
3 |
25 |
25 |
1273 |
3 |
35 |
32.5 |
1644 |
3 |
50 |
37.5 |
2107 |
3 |
70 |
35 |
2862 |
3 |
95 |
40 * |
4190 |
3 |
120 |
45 |
5176 |
3 |
150 |
50 |
6303 |
3 |
185 |
54 |
7698 |
3 |
240 |
63 |
9814 |
3 |
50 |
34.5 |
2560 |
3 |
70 |
40 |
3492 |
3 |
95 |
45 |
4790 |
3 |
120 |
50 |
5951 |
3 |
150 |
54 |
7090 |
5 |
1.5 |
15.5 |
301 |
5 |
2.5 |
17 |
373 |
5 |
4 |
18.5 |
480 |
5 |
6 |
20.5 |
638 |
5 |
10 |
22.5 |
900 |
5 |
16 |
26 |
1250 |
5 |
25 |
31 |
1903 |
5 |
35 |
32 |
2455 |
0.6 / 1 kV U-1000 R2V/XV/RV Cable Parameter
Single core |
Size Cross-Section in mm2 |
Perm. Current rating open air A |
Perm. Current rating burried A |
Voltage drop, 3 conductors V/A.km |
Max. outer diameter mm |
Nominal overall cable weight kg/km |
1.5 |
24 |
34 |
21.5 |
6.4 |
50 |
2.5 |
33 |
46 |
13.2 |
7.0 |
50 |
4 |
45 |
59 |
8.3 |
7.6 |
80 |
6 |
58 |
74 |
5.6 |
8.2 |
100 |
10 |
80 |
101 |
3.3 |
9.2 |
145 |
16 |
107 |
128 |
2.1 |
10.5 |
205 |
25 |
138 |
144 |
1.4 |
10.5 |
290 |
35 |
169 |
174 |
1.0 |
11.5 |
390 |
50 |
207 |
206 |
0.78 |
12.6 |
510 |
70 |
268 |
254 |
0.56 |
14.7 |
720 |
95 |
328 |
301 |
0.43 |
16.3 |
970 |
120 |
382 |
343 |
0.36 |
17.8 |
1210 |
150 |
441 |
387 |
0.31 |
20.2 |
1480 |
185 |
506 |
434 |
0.26 |
22.1 |
1835 |
240 |
599 |
501 |
0.22 |
24.9 |
2540 |
300 |
693 |
565 |
0.19 |
27.7 |
2945 |
400 |
825 |
662 |
0.17 |
31.6 |
2860 |
500 |
946 |
750 |
0.15 |
35.5 |
4890 |
Two cores |
Size Cross-Section in mm2 |
Perm. Current rating open air A |
Perm. Current rating burried A |
Voltage drop, 3 conductors V/A.km |
Max. outer diameter mm |
Nominal overall cable weight kg/km |
1.5 |
24.8 |
10.5 |
24 |
34 |
130 |
2.5 |
14.8 |
11.5 |
33 |
46 |
170 |
4 |
9.2 |
13.0 |
45 |
59 |
220 |
6 |
6.2 |
14.0 |
58 |
74 |
290 |
10 |
3.7 |
16.0 |
80 |
101 |
400 |
16 |
2.4 |
18.5 |
107 |
128 |
550 |
25 |
1.6 |
22.0 |
142 |
162 |
865 |
35 |
1.15 |
22.4 |
185 |
208 |
1145 |
50 |
|
24.2 |
225 |
247 |
1435 |
Three cores |
Size Cross-Section in mm2 |
Perm. Current rating open air A |
Perm. Current rating burried A |
Voltage drop, 3 conductors V/A.km |
Max. outer diameter mm |
Nominal overall cable weight kg/km |
1.5 |
21.4 |
11.0 |
22 |
29 |
145 |
2.5 |
13.2 |
12.5 |
30 |
40 |
190 |
4 |
8.2 |
13.5 |
40 |
51 |
250 |
6 |
5.5 |
15.0 |
52 |
64 |
340 |
10 |
3.3 |
17.0 |
71 |
88 |
485 |
16 |
2.1 |
16.5 |
96 |
111 |
690 |
25 |
1.37 |
23.5 |
127 |
144 |
1080 |
35 |
1.0 |
26.0 |
158 |
174 |
1435 |
50 |
0.76 |
29.0 |
192 |
206 |
1845 |
70 |
0.55 |
34.0 |
246 |
254 |
2560 |
95 |
0.42 |
38.5 |
298 |
301 |
3470 |
120 |
0.35 |
42.5 |
346 |
343 |
4410 |
150 |
0.30 |
47.5 |
395 |
387 |
5330 |
185 |
0.25 |
53.0 |
450 |
434 |
6570 |
240 |
0.19 |
59.5 |
538 |
501 |
8460 |
Three cores with smaller neutral conductor |
Size Cross-Section in mm2 |
Perm. Current rating open air A |
Perm. Current rating burried A |
Voltage drop, 3 conductors V/A.km |
Max. outer diameter mm |
Nominal overall cable weight kg/km |
50 |
0.78 |
31.1 |
35 |
190 |
204 |
70 |
0.55 |
35.1 |
35 |
242 |
252 |
70 |
0.57 |
36.2 |
50 |
242 |
252 |
95 |
0.44 |
40.6 |
50 |
293 |
302 |
120 |
0.36 |
45.4 |
70 |
339 |
345 |
150 |
0.31 |
49.5 |
70 |
390 |
386 |
240 |
0.23 |
61.5 |
95 |
522 |
504 |
Four cores |
Size Cross-Section in mm2 |
Perm. Current rating open air A |
Perm. Current rating burried A |
Voltage drop, 3 conductors V/A.km |
Max. outer diameter mm |
Nominal overall cable weight kg/km |
1.5 |
21.5 |
12.0 |
22 |
26 |
170 |
2.5 |
12.8 |
13.0 |
30 |
36 |
220 |
4 |
8.0 |
14.5 |
40 |
46 |
300 |
6 |
5.4 |
16.0 |
52 |
58 |
410 |
10 |
3.2 |
18.5 |
71 |
79 |
600 |
16 |
2.11 |
21.0 |
96 |
100 |
860 |
25 |
1.37 |
25.5 |
127 |
141 |
1340 |
35 |
1.0 |
28.5 |
158 |
174 |
1780 |
50 |
0.76 |
32.5 |
192 |
206 |
2330 |
70 |
0.55 |
34.5 |
246 |
254 |
3375 |
95 |
0.42 |
42.5 |
298 |
301 |
4345 |
120 |
0.35 |
47.5 |
346 |
343 |
5590 |
150 |
0.3 |
52.5 |
395 |
387 |
6650 |
185 |
0.25 |
59.0 |
450 |
434 |
8350 |
Five cores |
Size Cross-Section in mm2 |
Perm. Current rating open air A |
Perm. Current rating burried A |
Voltage drop, 3 conductors V/A.km |
Max. outer diameter mm |
Nominal overall cable weight kg/km |
1.5 |
21.5 |
13.0 |
22 |
26 |
200 |
2.5 |
13.2 |
14.5 |
30 |
36 |
275 |
4 |
8.2 |
16.0 |
30 |
46 |
365 |
6 |
5.5 |
17.5 |
52 |
58 |
490 |
10 |
3.3 |
20.0 |
71 |
79 |
725 |
16 |
2.1 |
23.0 |
96 |
100 |
1060 |
25 |
1.37 |
28.0 |
127 |
141 |
1610 |
35 |
1.0 |
30.5 |
157 |
170 |
2210 |
50 |
0.76 |
34.0 |
190 |
204 |
2930 |
70 |
0.54 |
43.0 |
242 |
252 |
4150 |
95 |
0.15 |
47.0 |
293 |
302 |
5540 |
How to Order R2V & RVFV Cables Price