A leading national provider of Medium Voltage (MV) Power Cable products for the electrical distribution sector in ranges from 2.4kV to 35 kV. Commonly referred to as MV cables, medium voltage cable solutions include but aren't limited to non-shielded Type MV-90 and copper tape shielded type MV-105 designs commonly found in many commercial and industrial applications.
Finding their use in power circuits in open air, conduit, or duct - a variety of constructions and types of Medium Voltage cable are available based on industrial application needs. From chemical plants, refineries, steel mills, and industrial plants to commercial buildings, utility substations, and generating stations.
ICEA S-94-649 5 kV – 46 kV Shielded Power Cables.
AEIC CS8 Standard for Utility Shielded Power Cables Rated 5 kV – 46 kV.
• 5 kV to 46 kV 100% and 133% IL Maximum conductor operation temperatures:
Wet and dry locations
• Normal: 105 °C
• Emergency: 140 °C
• Short Circuit: 250 °C
2. Dual sealed cable (Strand Filled on conductor and Neutral wires) meets the water penetration requirements in accordance with ICEA-T-34-664.
Finding their use in power circuits in open air, conduit, or duct - a variety of constructions and types of Medium Voltage cable are available based on industrial application needs. From chemical plants, refineries, steel mills, and industrial plants to commercial buildings, utility substations, and generating stations.
MV-90 MV-105 Cable Application
Primary power and distribution circuits in industrial and commercial installations, power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry locations, installed in underground, duct, or direct burial.MV-90 MV-105 Cable Standards
UL 1072 Medium Voltage Power Cables.ICEA S-94-649 5 kV – 46 kV Shielded Power Cables.
AEIC CS8 Standard for Utility Shielded Power Cables Rated 5 kV – 46 kV.
MV-90 MV-105 Cable Specifications
Maximum operating voltage:• 5 kV to 46 kV 100% and 133% IL Maximum conductor operation temperatures:
Wet and dry locations
• Normal: 105 °C
• Emergency: 140 °C
• Short Circuit: 250 °C
MV-90 MV-105 Cable Optional
1. Sealed conductor with strand filled compound passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.2. Dual sealed cable (Strand Filled on conductor and Neutral wires) meets the water penetration requirements in accordance with ICEA-T-34-664.
MV-90 MV-105 Cable Construction
- Conductor: Soft annealed uncoated copper compressed Class B per ASTM B496 or hard drawn Aluminum-1350 compressed Class B per ASTM B400.
- Conductor Shield: Semi conducting cross-linked polyethylene compound (XLPE compound).
- Insulation: Thermoset crosslinked polyethylene (XLPE). or TR-XLPE.
- Insulation Shield: Semi conducting cross-linked polyethylene compound (XLPE compound).
- Metallic Shield: Solid soft annealed copper wires per ASTM B3, helically applied and uniformly spaced. Or copper tape shield.
- Jacket: Extruded to fill, Black sunlight resistant linear low density polyethylene (LLDPE), with three Red Stripes. Or PVC.
5kV TR-XLPE Insulation type
Size AWG | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||||
or | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | ||
kcmil | in | AWG | mil | in | lb/kft | AWG | mil | in | lb/kft | |||
Copper 100% Insulation Level (90 mil) | ||||||||||||
2 | 7 | 0.5 | 6 | 14 | 50 | 0.81 | 469 | 16 | 14 | 50 | 0.81 | 589 |
1 | 19 | 0.54 | 7 | 14 | 50 | 0.84 | 547 | 13 | 12 | 50 | 0.88 | 730 |
1/0 | 19 | 0.58 | 9 | 14 | 50 | 0.88 | 653 | 16 | 12 | 50 | 0.92 | 870 |
2/0 | 19 | 0.63 | 11 | 14 | 50 | 0.93 | 779 | 13 | 10 | 50 | 1 | 1089 |
3/0 | 19 | 0.68 | 14 | 14 | 50 | 0.98 | 941 | 16 | 10 | 50 | 1.05 | 1309 |
4/0 | 19 | 0.73 | 18 | 14 | 50 | 1.03 | 1146 | 16 | 9 | 50 | 1.14 | 1613 |
250 | 37 | 0.79 | 13 | 12 | 50 | 1.12 | 1340 | — | — | — | — | — |
350 | 37 | 0.89 | 18 | 12 | 50 | 1.23 | 1785 | — | — | — | — | — |
500 | 37 | 1.02 | 17 | 10 | 50 | 1.42 | 2535 | — | — | — | — | — |
750 | 61 | 1.21 | 20 | 9 | 80 | 1.7 | 3731 | — | — | — | — | — |
1000 | 61 | 1.36 | 26 | 9 | 80 | 1.85 | 4807 | — | — | — | — | — |
Aluminum 100% Insulation Level (90 mil) | ||||||||||||
2 | 1 | 0.48 | 6 | 14 | 50 | 0.78 | 311 | 10 | 14 | 50 | 0.78 | 360 |
2 | 7 | 0.5 | 6 | 14 | 50 | 0.81 | 325 | 10 | 14 | 50 | 0.81 | 374 |
1 | 19 | 0.54 | 6 | 14 | 50 | 0.84 | 355 | 13 | 14 | 50 | 0.84 | 439 |
1/0 | 1 | 0.54 | 6 | 14 | 50 | 0.85 | 370 | 16 | 14 | 50 | 0.85 | 491 |
1/0 | 19 | 0.58 | 6 | 14 | 50 | 0.88 | 389 | 16 | 14 | 50 | 0.88 | 510 |
2/0 | 19 | 0.62 | 7 | 14 | 50 | 0.93 | 444 | 13 | 12 | 50 | 0.96 | 629 |
3/0 | 19 | 0.67 | 9 | 14 | 50 | 0.98 | 519 | 16 | 12 | 50 | 1.01 | 738 |
4/0 | 19 | 0.73 | 11 | 14 | 50 | 1.03 | 606 | 13 | 10 | 50 | 1.11 | 921 |
250 | 37 | 0.79 | 13 | 14 | 50 | 1.09 | 686 | 16 | 10 | 50 | 1.17 | 1071 |
350 | 37 | 0.89 | 18 | 14 | 50 | 1.19 | 879 | 16 | 9 | 50 | 1.29 | 1356 |
500 | 37 | 1.02 | 16 | 12 | 50 | 1.38 | 1208 | 29 | 10 | 50 | 1.42 | 1823 |
750 | 61 | 1.22 | 15 | 10 | 80 | 1.69 | 1798 | — | — | — | — | — |
1000 | 61 | 1.37 | 16 | 9 | 80 | 1.86 | 2292 | — | — | — | — | — |