DIN VDE 0276 Description
DIN VDE 0276 is the widely used German standard for cables with extruded insulation used in power distribution systems.This standard covers a significant percentage of power cables used across the European continent. It covers the various cable construction and test methods, and it consists of the following parts:
DIN VDE 0276 | Scope |
Part 1 | General requirements |
Part 10-C | Construction, dimensions and test requirements of single-core power cables with XLPE-insulation and with PE-sheath or PVC-sheath for rated voltage of 6/10 kV, 12/20 kV and 18/30 kV and of three-core power cables with XLPE-insulation and with PE-sheath or PVC-sheath for rated voltage of 6/10 kV for fixed installations |
Part 603 | Distribution cables of nominal voltages 0.6/1kV |
Part 604 | Power cables of nominal voltages 0.6/1kV with special fire performance for use in power stations |
Part 604 & 605 | Additional test methods |
Part 620 | Distribution cables of nominal voltages 3.6 to 20.8/36kV |
Part 1000 | Current carrying capacity, general, conversion factors |
Part 1001 | Tests on cables laid with nominal voltages 6/10kV, 12/20kV and 18/30kV with PVC insulation, VPE insulation or paper insulation |
VDE0276 Cable Types
DIN VDE 0276 0.6/1 kV NA2X2Y Cable AL/XLPE/HDPE
DIN VDE 0276 0.6/1 kV NAYY-J/NAYY-O NAYY Cable AL/PVC/PVC
DIN VDE 0276 0.6/1 kV NA2XY NA2XY-J NA2XY-O kabel AL/XLPE/PVC
DIN VDE 0276 0.6/1 kV NYCWY Cable CU/PVC/CWS/PVC
DIN VDE 0276 0.6/1 kV NAY2Y-J NAY2Y Cable AL/PVC/HDPE
DIN VDE 0276 0.6/1 kV NYCY Cable CU/PVC/CWS/PVC
DIN VDE 0276 0.6/1 kV NAYCWY Cable AL/PVC/CWS/PVC
DIN VDE 0276 0.6/1(1.2)kV NYY-JNYY-O NYY Cable Cu/PVC/PVC
Low Voltage PVC Insulated NYY Power Cable Construction
Conductor
shaped: RE=circular solid, CC=compacted circular stranded, SM=sector shaped stranded
Insulation
PVC Compound Insulation
Colour identification
1 Core: Red or Black
2 Cores: Red, Black
3 Cores: Red, Yellow, Blue
4 Cores: Red, Yellow, Blue, Black
5 Cores: Red, Yellow, Blue, Black, Green
Above 5 Cores: Black Cores with White numerals
The above identifying can be changed as order
Bedding/Inner Sheath PVC Compound
Note::
The armored material of single core cable should be non-magnetic or magnetic reduced structure. Generallly, single core armored cable (which uses steel or steel wire armored cable) only applies to DC occasions.
Single Core NYY NAYY Cable
Type | Nominal section area mm2 |
Conductor diameter mm |
Nominal thickness of insulation mm |
Nominal sheath thickness mm |
Approx. overall diameter mm |
Approx.weight of cable kg/km |
Maximum DC resistance of the conductor Ω/km |
||
Cu | Al | 20℃ Cu | 20℃ Al | ||||||
NYY NAYY |
1×1.5 RE 1×2.5 RE 1×4 RE 1×6 RE 1×10 CC |
1.38 1.78 2.24 2.76 3.8 |
0.8 0.8 1.0 1.0 1.0 |
1.4 1.4 1.4 1.4 1.4 |
5.8 6.2 7.1 7.6 8.6 |
49.3 62.2 86.4 109.8 156.7 |
- 46.6 61.6 72.6 94.8 |
12.1 7.41 4.61 3.08 1.83 |
- 12.1 7.41 4.61 3.08 |
1×16 CC 1×25 CC 1×35 CC 1×50 CC 1×70 CC |
4.8 6.0 7.0 8.4 10.0 |
1.0 1.2 1.2 1.4 1.4 |
1.4 1.4 1.4 1.4 1.4 |
9.6 11.2 12.2 14.0 15.7 |
221.0 324.1 426.8 586.0 787.5 |
122.0 169.4 210.2 276.6 354.4 |
1.15 0.727 0.524 0.387 0.268 |
1.91 1.20 0.868 0.641 0.443 |
|
1×95 CC 1×120 CC 1×150 CC 1×185 CC 1×240 CC |
11.5 13.0 14.5 16.2 18.4 |
1.6 1.6 1.8 2.0 2.2 |
1.5 1.5 1.6 1.7 1.8 |
17.7 19.3 21.3 23.6 26.4 |
1050.5 1298.2 1611.6 1977.4 2537.7 |
462.7 555.7 683.6 832.8 1052.9 |
0.193 0.153 0.124 0.0991 0.0754 |
0.320 0.253 0.206 0.164 0.125 |