Single Core ICEA S-66-524 / MEA 35kv Spaced Aerial Cable
Spaced Aerial Cable Application
This kind of spaced aerial cable ( SAC cable) is used for aerial power transmission at 15/25/35 maximum system voltage. the phase to phase voltage is 10/20/33KV. This standard applies of supported spacer cable. These conductors are intended primarily for the distribution of electrical energy under normal conditions of overhead (aerial) installations. They are considered as covered conductors therefore the cables carry no voltage rating. The conductors must be installed on insulators and/or spacers adequate for the service voltage. The user may want to give consideration to the dielectric compatibility of the covering, insulator, spacer.
Spaced Aerial Cable Description
The conductors are stranded,circular compressed aluminum. The conductor screen is the extruded Semi-conducting conductor shield in Black. The inner Insulation is mainly natural color thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE). And the outer Insulation is mainly thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE) in Black or Grey with Weather or UV resistant. This standard covers both thermoplastic and cross linked polyethylene constructions, rated for 75°C or 90°C normal service temperature.
Spaced Aerial Cable Specifications
• ICEA S-66-524 Cross-Linked-Thermosetting-Polyethylene-Insulated Wire and Cable for The Transmission and Distribution of Electrical Energy
• GB/T 14049 (Equal to IEC 60502-2) Aerial Insulated Cables For Rated Voltage of 10kV
15kV SAC Spaced Aerial Cable
Nominal Size Min.No.
of Wires
Covering Thickness Cable Diameter Min. Breaking Load Weight
Conductor Shield Inner Layer Outer Layer
mm2 No. mm mm mm mm N kg/km
3-Layer 15kV AAC/XLPE/XLPE
25 6 0.60 1.91 1.91 15.2 3762 218
35 6 0.60 1.91 1.91 16.2 5177 258
50 6 0.60 1.91 1.91 17.3 7011 307
70 12 0.60 1.91 1.91 19.0 10354 387
95 15 0.60 1.91 1.91 20.8 13727 482
120 15 0.60 1.91 1.91 22.0 17339 564
150 15 0.60 1.91 1.91 23.7 21033 660
185 30 0.60 1.91 1.91 25.3 26732 780
240 30 0.60 1.91 1.91 27.6 34679 968
25kV SAC Cable
Nominal Size Min. No.
of Wires
Covering Thickness Cable Diameter Min. Breaking Load Weight
Conductor Shield Inner Layer Outer Layer
mm2 No. mm mm mm mm N kg/km
3-Layer 25kV AAC/XLPE/XLPE
25 6 0.70 3.18 3.18 20.1 3762 351
35 6 0.70 3.18 3.18 21.1 5177 398
50 6 0.70 3.18 3.18 22.2 7011 455
70 12 0.70 3.18 3.18 23.9 10354 548
95 15 0.70 3.18 3.18 25.7 13727 657
120 15 0.70 3.18 3.18 26.9 17339 748
150 15 0.70 3.18 3.18 28.6 21033 856
185 30 0.70 3.18 3.18 30.2 26732 989
240 30 0.70 3.18 3.18 32.5 34679 1195
35kV SAC Cable
Nominal Size Min. No.
of Wires
Covering Thickness Cable Diameter Min. Breaking Load Weight
Conductor Shield Inner Layer Outer Layer
mm2 No. mm mm mm mm N kg/km
3-Layer 35kV AAC/XLPE/XLPE
25 6 0.70 4.45 3.18 22.6 3762 433
35 6 0.70 4.45 3.18 23.6 5177 485
50 6 0.70 4.45 3.18 24.7 7011 545
70 12 0.70 4.45 3.18 26.4 10354 645
95 15 0.70 4.45 3.18 28.2 13727 761
120 15 0.70 4.45 3.18 29.4 17339 856
150 15 0.70 4.45 3.18 31.1 21033 971
185 30 0.70 4.45 3.18 32.7 26732 1110
240 30 0.70 4.45 3.18 35.0 34679 1324
15kV SAC Cable
Nominal Size Min. No.
of Wires
Covering Thickness Cable Diameter Min. Breaking Load Weight
Conductor Shield Inner Layer Outer Layer
mm2 No. mm mm mm mm N kg/km
3-Layer 15kV AAC/XLPE/HDPE
25 6 0.60 1.91 1.91 15.2 3762 221
35 6 0.60 1.91 1.91 16.2 5177 261
50 6 0.60 1.91 1.91 17.3 7011 310
70 12 0.60 1.91 1.91 19.0 10354 390
95 15 0.60 1.91 1.91 20.8 13727 486
120 15 0.60 1.91 1.91 22.0 17339 568
150 15 0.60 1.91 1.91 23.7 21033 664
185 30 0.60 1.91 1.91 25.3 26732 785
240 30 0.60 1.91 1.91 27.6 34679 973
25kV SAC Cable  
Nominal Size Min. No.
of Wires
Covering Thickness Cable Diameter Min. Breaking Load Weight
Conductor Shield Inner Layer Outer Layer
mm2 No. mm mm mm mm N kg/km
3-Layer 25kV AAC/XLPE/HDPE
25 6 0.70 3.18 3.18 20.1 3762 356
35 6 0.70 3.18 3.18 21.1 5177 404
50 6 0.70 3.18 3.18 22.2 7011 461
70 12 0.70 3.18 3.18 23.9 10354 555 
95 15 0.70 3.18 3.18 25.7 13727 664
120 15 0.70 3.18 3.18 26.9 17339 755
150 15 0.70 3.18 3.18 28.6 21033 864
185 30 0.70 3.18 3.18 30.2 26732 997
240 30 0.70 3.18 3.18 32.5 34679 1203
35kV SAC Cable 
Nominal Size Min. No.
of Wires
Covering Thickness Cable Diameter Min. Breaking Load Weight
Conductor Shield Inner Layer Outer Layer
mm2 No. mm mm mm mm N kg/km
3-Layer 35kV AAC/XLPE/HDPE
25 6 0.70 4.45 3.18 22.6 3762 439
35 6 0.70 4.45 3.18 23.6 5177 491
50 6 0.70 4.45 3.18 24.7 7011 552
70 12 0.70 4.45 3.18 26.4 10354 652
95 15 0.70 4.45 3.18 28.2 13727 768
120 15 0.70 4.45 3.18 29.4 17339 864
150 15 0.70 4.45 3.18 31.1 21033 980
185 30 0.70 4.45 3.18 32.7 26732 1119
240 30 0.70 4.45 3.18 35.0 34679 1334

Contact Us, Now.
24-hour service hotline
Contact online customer service
Add: Technology Building, Tongbai Road, Zhongyuan District, Zhengzhou, Henan, China.
Related products
Tree Wire(ANSI/ICEA S-121-733)
3-Layer Tree Wire(ANSI/ICEA S-121-733)
ACSR-OC ACSR/AW-OC ACSR/AW-TR/OC(KS C 3138)
ACSR-OC ACSR/AW-OC ACSR/AW-TR/OC(KS C 3138)
MV Aerial Bundled Cable(ASTM) Covered Aerial MV Cable Tree Wire Spacer Cable
MV Covered Aerial Cable(ASTM)
MVCC/MVC Medium Voltage Covered Conductors(BS EN 50397)
MVCC/MVC Medium Voltage Covered Conductors(BS EN 50397)
Related cases
Supply and Delivery of 80 Km OPGW Lane with its Equipment in Iraq
Supply and Delivery of 80 Km OPGW Lane with its Equipment in Iraq
Supply and provide optical fiber overhead ground wire opgw to overhead power transmission linesOverhead Stainless Steel Tube Optical Fiber Composite Ground Wire
Air Blown Micro Fiber Optical Cable
Air Blown Micro Fiber Optical Cable
Air Blown Micro Fiber Optical CableAir-blown micro-cables & micro-tubes, applied in a variety of application scenarios, improve the utilization ratio of pipe ho
ADSS 24-wire anti-rodent type fiber optic cable
Ecuador ADSS FRP Defender-Anti Rodent Fiber Optic Cable for Sale
All-Dielectric Self-Supporting (ADSS) FiberGlass Rods (FRP) Defender This design combines enhanced optical reliability with the highest degree of rodent resistance available in an all-dielectric cable. It also can be used as an all-dielectric direct buried cable solution. Up to 144 fibers Maximum rated design tension up to 4,496 lb (20 kN) Crush up to 571 lb/in (1 kN/cm)