Spaced Aerial Cable Application
This kind of spaced aerial cable ( SAC cable) is used for aerial power transmission at 15/25/35 maximum system voltage. the phase to phase voltage is 10/20/33KV. This standard applies of supported spacer cable. These conductors are intended primarily for the distribution of electrical energy under normal conditions of overhead (aerial) installations. They are considered as covered conductors therefore the cables carry no voltage rating. The conductors must be installed on insulators and/or spacers adequate for the service voltage. The user may want to give consideration to the dielectric compatibility of the covering, insulator, spacer.
Spaced Aerial Cable Description
The conductors are stranded,circular compressed aluminum. The conductor screen is the extruded Semi-conducting conductor shield in Black. The inner Insulation is mainly natural color thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE). And the outer Insulation is mainly thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE) in Black or Grey with Weather or UV resistant. This standard covers both thermoplastic and cross linked polyethylene constructions, rated for 75°C or 90°C normal service temperature.
Spaced Aerial Cable Specifications
• ICEA S-66-524 Cross-Linked-Thermosetting-Polyethylene-Insulated Wire and Cable for The Transmission and Distribution of Electrical Energy
• GB/T 14049 (Equal to IEC 60502-2) Aerial Insulated Cables For Rated Voltage of 10kV
This kind of spaced aerial cable ( SAC cable) is used for aerial power transmission at 15/25/35 maximum system voltage. the phase to phase voltage is 10/20/33KV. This standard applies of supported spacer cable. These conductors are intended primarily for the distribution of electrical energy under normal conditions of overhead (aerial) installations. They are considered as covered conductors therefore the cables carry no voltage rating. The conductors must be installed on insulators and/or spacers adequate for the service voltage. The user may want to give consideration to the dielectric compatibility of the covering, insulator, spacer.
Spaced Aerial Cable Description
The conductors are stranded,circular compressed aluminum. The conductor screen is the extruded Semi-conducting conductor shield in Black. The inner Insulation is mainly natural color thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE). And the outer Insulation is mainly thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE) in Black or Grey with Weather or UV resistant. This standard covers both thermoplastic and cross linked polyethylene constructions, rated for 75°C or 90°C normal service temperature.
Spaced Aerial Cable Specifications
• ICEA S-66-524 Cross-Linked-Thermosetting-Polyethylene-Insulated Wire and Cable for The Transmission and Distribution of Electrical Energy
• GB/T 14049 (Equal to IEC 60502-2) Aerial Insulated Cables For Rated Voltage of 10kV
15kV SAC Spaced Aerial Cable
25kV SAC Cable
35kV SAC Cable
15kV SAC Cable
25kV SAC Cable
35kV SAC Cable
Nominal Size | Min.No. of Wires |
Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | |||
Conductor Shield | Inner Layer | Outer Layer | ||||||
mm2 | No. | mm | mm | mm | mm | N | kg/km | |
3-Layer 15kV AAC/XLPE/XLPE | ||||||||
25 | 6 | 0.60 | 1.91 | 1.91 | 15.2 | 3762 | 218 | |
35 | 6 | 0.60 | 1.91 | 1.91 | 16.2 | 5177 | 258 | |
50 | 6 | 0.60 | 1.91 | 1.91 | 17.3 | 7011 | 307 | |
70 | 12 | 0.60 | 1.91 | 1.91 | 19.0 | 10354 | 387 | |
95 | 15 | 0.60 | 1.91 | 1.91 | 20.8 | 13727 | 482 | |
120 | 15 | 0.60 | 1.91 | 1.91 | 22.0 | 17339 | 564 | |
150 | 15 | 0.60 | 1.91 | 1.91 | 23.7 | 21033 | 660 | |
185 | 30 | 0.60 | 1.91 | 1.91 | 25.3 | 26732 | 780 | |
240 | 30 | 0.60 | 1.91 | 1.91 | 27.6 | 34679 | 968 |
Nominal Size | Min. No. of Wires |
Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | ||
Conductor Shield | Inner Layer | Outer Layer | |||||
mm2 | No. | mm | mm | mm | mm | N | kg/km |
3-Layer 25kV AAC/XLPE/XLPE | |||||||
25 | 6 | 0.70 | 3.18 | 3.18 | 20.1 | 3762 | 351 |
35 | 6 | 0.70 | 3.18 | 3.18 | 21.1 | 5177 | 398 |
50 | 6 | 0.70 | 3.18 | 3.18 | 22.2 | 7011 | 455 |
70 | 12 | 0.70 | 3.18 | 3.18 | 23.9 | 10354 | 548 |
95 | 15 | 0.70 | 3.18 | 3.18 | 25.7 | 13727 | 657 |
120 | 15 | 0.70 | 3.18 | 3.18 | 26.9 | 17339 | 748 |
150 | 15 | 0.70 | 3.18 | 3.18 | 28.6 | 21033 | 856 |
185 | 30 | 0.70 | 3.18 | 3.18 | 30.2 | 26732 | 989 |
240 | 30 | 0.70 | 3.18 | 3.18 | 32.5 | 34679 | 1195 |
Nominal Size | Min. No. of Wires |
Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | ||
Conductor Shield | Inner Layer | Outer Layer | |||||
mm2 | No. | mm | mm | mm | mm | N | kg/km |
3-Layer 35kV AAC/XLPE/XLPE | |||||||
25 | 6 | 0.70 | 4.45 | 3.18 | 22.6 | 3762 | 433 |
35 | 6 | 0.70 | 4.45 | 3.18 | 23.6 | 5177 | 485 |
50 | 6 | 0.70 | 4.45 | 3.18 | 24.7 | 7011 | 545 |
70 | 12 | 0.70 | 4.45 | 3.18 | 26.4 | 10354 | 645 |
95 | 15 | 0.70 | 4.45 | 3.18 | 28.2 | 13727 | 761 |
120 | 15 | 0.70 | 4.45 | 3.18 | 29.4 | 17339 | 856 |
150 | 15 | 0.70 | 4.45 | 3.18 | 31.1 | 21033 | 971 |
185 | 30 | 0.70 | 4.45 | 3.18 | 32.7 | 26732 | 1110 |
240 | 30 | 0.70 | 4.45 | 3.18 | 35.0 | 34679 | 1324 |
Nominal Size | Min. No. of Wires |
Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | |||
Conductor Shield | Inner Layer | Outer Layer | ||||||
mm2 | No. | mm | mm | mm | mm | N | kg/km | |
3-Layer 15kV AAC/XLPE/HDPE | ||||||||
25 | 6 | 0.60 | 1.91 | 1.91 | 15.2 | 3762 | 221 | |
35 | 6 | 0.60 | 1.91 | 1.91 | 16.2 | 5177 | 261 | |
50 | 6 | 0.60 | 1.91 | 1.91 | 17.3 | 7011 | 310 | |
70 | 12 | 0.60 | 1.91 | 1.91 | 19.0 | 10354 | 390 | |
95 | 15 | 0.60 | 1.91 | 1.91 | 20.8 | 13727 | 486 | |
120 | 15 | 0.60 | 1.91 | 1.91 | 22.0 | 17339 | 568 | |
150 | 15 | 0.60 | 1.91 | 1.91 | 23.7 | 21033 | 664 | |
185 | 30 | 0.60 | 1.91 | 1.91 | 25.3 | 26732 | 785 | |
240 | 30 | 0.60 | 1.91 | 1.91 | 27.6 | 34679 | 973 |
Nominal Size | Min. No. of Wires |
Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | ||
Conductor Shield | Inner Layer | Outer Layer | |||||
mm2 | No. | mm | mm | mm | mm | N | kg/km |
3-Layer 25kV AAC/XLPE/HDPE | |||||||
25 | 6 | 0.70 | 3.18 | 3.18 | 20.1 | 3762 | 356 |
35 | 6 | 0.70 | 3.18 | 3.18 | 21.1 | 5177 | 404 |
50 | 6 | 0.70 | 3.18 | 3.18 | 22.2 | 7011 | 461 |
70 | 12 | 0.70 | 3.18 | 3.18 | 23.9 | 10354 | 555 |
95 | 15 | 0.70 | 3.18 | 3.18 | 25.7 | 13727 | 664 |
120 | 15 | 0.70 | 3.18 | 3.18 | 26.9 | 17339 | 755 |
150 | 15 | 0.70 | 3.18 | 3.18 | 28.6 | 21033 | 864 |
185 | 30 | 0.70 | 3.18 | 3.18 | 30.2 | 26732 | 997 |
240 | 30 | 0.70 | 3.18 | 3.18 | 32.5 | 34679 | 1203 |
Nominal Size | Min. No. of Wires |
Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | ||
Conductor Shield | Inner Layer | Outer Layer | |||||
mm2 | No. | mm | mm | mm | mm | N | kg/km |
3-Layer 35kV AAC/XLPE/HDPE | |||||||
25 | 6 | 0.70 | 4.45 | 3.18 | 22.6 | 3762 | 439 |
35 | 6 | 0.70 | 4.45 | 3.18 | 23.6 | 5177 | 491 |
50 | 6 | 0.70 | 4.45 | 3.18 | 24.7 | 7011 | 552 |
70 | 12 | 0.70 | 4.45 | 3.18 | 26.4 | 10354 | 652 |
95 | 15 | 0.70 | 4.45 | 3.18 | 28.2 | 13727 | 768 |
120 | 15 | 0.70 | 4.45 | 3.18 | 29.4 | 17339 | 864 |
150 | 15 | 0.70 | 4.45 | 3.18 | 31.1 | 21033 | 980 |
185 | 30 | 0.70 | 4.45 | 3.18 | 32.7 | 26732 | 1119 |
240 | 30 | 0.70 | 4.45 | 3.18 | 35.0 | 34679 | 1334 |