Core Wire (INVAR) : Aluminum-clad INVAR Wire/High Tensile Strength Aluminum-clad INVAR Wire
Conductor (STAL) : Super Thermal Resistant Aluminum Alloy Wire used for continuous allowable temperature up to 210°C
STACIR Standard
IEC, ASTM, JCS 1405
•Double current carrying capacity of the same size ACSR
•No limitation for application area: Heavy wind, snow & galloping area
•Equivalent Sag-tension properties to conventional ACSR
•No modification & reinforcement on existing tower
•Easy installation with same method & equipments as ACSR's
•Low cost and short construction period
•Proved long-term reliability
STACIR Application
Hi-TACSR/AW is used for electric power transmission lines. River-crossing area, seaside district and over seas area, long span, mountain area etc.
STACIR/AW Data Sheet
| Size | Section Area | Conductor Construction | Approx. Overall diameter | Approx. Overall weight | Maximum DC resistance at 20oC | Modulus of Elasticity | Coefficient of Linear Expansion | Ultimate Tensile Strength | Current Carrying Capacity | ||
| 
 | STAL | AL-INVAR | STAL | AL-INVAR | |||||||
| mm2 | mm2 | mm2 | No.xmm | No.xmm | mm | kg/km | Ω/km | Kgf/ mm2 | x10-6/oC | Kgf | A | 
| 160 | 159.30 | 37.16 | 30 x 2.60 | 7 x 2.60 | 18.20 | 441.7 | 0.1745 | 6,140 | 16.0 | 6,140 | 909 | 
| 240 | 241.30 | 56.29 | 30 x 3.20 | 7 x 3.20 | 22.40 | 669.1 | 0.1159 | 9,170 | 16.0 | 9,170 | 1,203 | 
| 330 | 326.80 | 52.84 | 26 x 4.00 | 7 x 3.10 | 25.30 | 905.1 | 0.0869 | 10,000 | 17.5 | 10,000 | 1,452 | 
| 410 | 413.40 | 67.35 | 26 x 4.50 | 7 x 3.50 | 28.50 | 1,145.5 | 0.0686 | 12,720 | 17.5 | 12,720 | 1,708 | 
| 480 (Rail) | 483.84 | 33.54 | 45 x 3.70 | 7 x 2.47 | 29.61 | 1,340.7 | 0.0600 | 10,500 | 20.0 | 10,500 | 1,812 | 
| 480(Cardinal) | 484.52 | 62.81 | 54 x 3.38 | 7 x 3.38 | 30.42 | 1,343.5 | 0.0591 | 13,280 | 18.3 | 13,280 | 1,846 | 
Hi-STACIR/AW
| Size | Section Area | Conductor Construction | Approx. Overall diameter | Approx. Overall weight | Maximum DC resistance at 20oC | Modulus of Elasticity | Coefficient of Linear Expansion | Ultimate Tensile Strength | Current Carrying Capacity | ||
| 
 | STAL | Hi-AL-INVAR | STAL | Hi-AL-INVAR | |||||||
| mm2 | mm2 | mm2 | No.xmm | No.xmm | mm | kg/km | Ω/km | Kgf/ mm2 | x10-6/oC | Kgf | A | 
| 160 | 159.30 | 37.16 | 30/2.60 | 7/2.60 | 18.20 | 706.9 | 0.1745 | 8,040 | 16.0 | 6,500 | 909 | 
| 240 | 241.30 | 56.29 | 30/3.20 | 7/3.20 | 22.40 | 1070.8 | 0.1159 | 8,040 | 16.0 | 9,700 | 1,203 | 
| 330 | 326.80 | 52.84 | 26/4.00 | 7/3.10 | 25.30 | 1282.1 | 0.0869 | 7,580 | 17.5 | 10,500 | 1,452 | 
| 410 | 413.40 | 67.35 | 26/4.50 | 7/3.50 | 28.50 | 1626.1 | 0.0686 | 7,590 | 17.5 | 13,300 | 1,708 | 
| 480 (Rail) | 483.84 | 33.54 | 45/3.70 | 7/2.47 | 29.61 | 1580.0 | 0.0600 | 6,900 | 20.0 | 11,000 | 1,812 | 
| 480(Cardinal) | 484.52 | 62.81 | 54/3.38 | 7/3.38 | 30.42 | 1795.7 | 0.0591 | 7,470 | 18.3 | 13,800 | 1,846 | 
 
                     
                 
                     
                         
                         
                         
                         
		 
		 
		 
                         
                    